Danfoss AK-SM 8xxA Controllers Affected by Unauthenticated Stack Buffer Overflow (CVE-2026-129713)
Article Content
- •CVE-2026-129713 (CVSS 9.3) is an unauthenticated stack-based buffer overflow in Danfoss AK-SM 8xxA controllers, versions 5.4.0 and earlier.
- •Successful exploitation may cause webserver restart; Danfoss describes arbitrary code execution as hypothetical.
- •No patch is yet available; the fix is planned for AK-SM 800A version 5.5.x.
- •Interim mitigations: keep devices off the internet, require VPN access, enable Strict Mode, and use strong passwords.
- •A public proof-of-concept was reported on 2026-11-24; no confirmed in-the-wild exploitation is reported.
CISA published advisory ICSA-26-328-03 on 2026-11-24 describing a stack-based buffer overflow (CWE-121) in Danfoss AK-SM 8xxA Series controllers, tracked as CVE-2026-129713 with a CVSS score of 9.3. Danfoss's own advisory DSA-2026-12-01 states the flaw is in an unauthenticated CGI handler, so remote attackers can send crafted HTTP/S POST requests to cause memory corruption and a webserver restart, and Danfoss describes potential arbitrary code execution with webserver privileges as hypothetical. Authentication is not required to exploit the flaw. The CISA advisory lists affected versions as AK-SM8xxA <=5.4.0, deployed worldwide in commercial facilities, with Danfoss headquartered in Denmark. The vulnerability was reported to CISA by Carlo Meijer of Midnight Blue. Danfoss states it will be fixed in an upcoming AK-SM 800A software release (version 5.5.x) and will remove the option to disable Strict Mode. Until a patch is available, Danfoss recommends avoiding internet exposure or public IP assignment, restricting remote access to secure VPNs or protected networks, enabling Strict Mode, and using strong unique passwords. The KNOWN CVE DATES record lists publication on 2026-11-20 and a first public proof-of-concept on 2026-11-24; neither source reports confirmed exploitation in the wild.
Ask AI about this cluster
Answers cite the sources they use
Timeline
More articles in this cluster (3)
Following this threat?
Track Danfoss and CVE-2026-129713 in your own feed — you're alerted when they show up in new reporting, leak sites or exploitation.
Free account · no card needed